Page Loading...
Littelfuse
SE-701-0D LITTELFUSE GROUND-FAULT MONITOR 24 VDC SUPPLY

Mouse over image to zoom, click to enlarge

Description: Littelfuse® Ground Fault Monitor, Series: SE-701, 12/24 V DC, 0 to 5 V DC Analog Output, Isolated NO (1 Form A), NC (1 Form B) Output Contact, 24 to 12 AWG Wire Clamping Terminal, DIN Rail Mount, 3 in H x 2.2 in W x 4.5 in D

Manufacturer PN: SE-701-0D

UPC:  07945898905

Kendall Electric Inc PN: 3903075

Invoice Description:

SE-701-0D LITTELFUSE GROUND-FAULT MONITOR 24 VDC SUPPLY


SPEC SHEET

▸ See All in Ground Fault Relay

 

Littelfuse® SE-701-0D Ground Fault Monitor, 12/24 V DC, 0 to 5 V DC Analog Output, Isolated NO (1 Form A), NC (1 Form B) Output Contact, 24 to 12 AWG Wire Clamping Terminal, DIN Rail Mount

Log In for Pricing and Availability

Note: Lead times are estimates only

 
 

Description

The SE-701 is a microprocessor based ground fault relay for resistance and solidly grounded systems. In addition to common systems, it is uniquely suited for use on systems with significant harmonic content. The SE-701 can provide main plant protection, feeder level protection or individual load protection. Proper current transformer selection provides the desired pickup range. The output contacts can be connected for use in protective tripping circuits or in alarm indication circuits. The analog output can be used with a PLC or a meter.
Littelfuse® Ground Fault Monitor, Series: SE-701, 12/24 V DC, 0 to 5 V DC Analog Output, Isolated NO (1 Form A), NC (1 Form B) Output Contact, 24 to 12 AWG Wire Clamping Terminal, DIN Rail Mount, 3 in H x 2.2 in W x 4.5 in D

Specifications

 Analog Output 0 to 5 V DC
 Brand Name Littelfuse®
 Dimensions 3 in H x 2.2 in W x 4.5 in D
 Manufacturer Part Number SE-701-0D
 Mounting Type DIN Rail
 PART NUMBER KEYWORDS SE-701-0D ; SE7010D ; 11795165 ; 079458989052 ; 79458989052 ; 07945898905 ; 00079458989052
 Series SE-701
 Specifications Isolated NO (1 Form A), NC (1 Form B) Output Contact, 24 to 12 AWG Wire Clamping Terminal
 Standards/Approvals cCSAus File No. LR53428|UL File No. E340889|CE Certified|C-Tick N11659|FCC Approved|PPROP65: This product can expose you to chemicals including nickel, which is known to the State of California to cause cancer
 Voltage Rating 12/24 V DC

Features

▪ Universal power supply allows operation in application where one side of PT is faulted, provides flexibility for numerous applications
▪ Adjustable pickup (1 to 99%) trip setting based on input CT primary, allows use with any CT, minimum 50 mA with EFCT series
▪ Adjustable time delay (50 ms to 2.5 s) - adjustable trip delay allows quick protection and system coordination
▪ Form A and form B ground fault output contacts for operation of separate annunciation and trip circuits
▪ Analog output (0 to 5 VDC) allows for connecting an optional meter (PGA-0500) or a control system
▪ CT-loop monitoring - alarms when CT is not connected
▪ Selectable DFT or peak detection filtering compatible with variable-speed drives
▪ Harmonic filtering eliminates nuisance tripping
▪ Non-volatile trip memory retains trip state when de-energized to simplify troubleshooting
▪ No calibration required, saves on maintenance cost
 
Time Zone 
 
 
 