Page Loading...
Littelfuse
LITTELFUSE SE-704-0D EARTH-LEAKAGE MONITOR 24-VDC

Mouse over image to zoom, click to enlarge

Description: Littelfuse® Earth Leakage Monitor, Series: SE-704, 12/24 VDC, 0 to 5 VDC, 0 to 1 mA Analog Output, Isolated NO (1 Form A), NC (1 Form B) Output Contact, 24 to 12 AWG Wire Clamping Terminal, DIN Rail/Surface Mount, 3 in H x 2.2 in W x 4.5 in D

Manufacturer PN: SE-704-0D

UPC:  07945898913

Kendall Electric Inc PN: 4360731

Invoice Description:

LITTELFUSE SE-704-0D EARTH-LEAKAGE MONITOR 24-VDC


SPEC SHEET

▸ See All in Ground Fault Relay

 

Littelfuse® SE-704-0D Earth Leakage Monitor, 12/24 VDC, 0 to 5 VDC, 0 to 1 mA Analog Output, Isolated NO (1 Form A), NC (1 Form B) Output Contact, 24 to 12 AWG Wire Clamping Terminal, DIN Rail/Surface Mount

Log In for Pricing and Availability

Note: Lead times are estimates only

 
 

Description

The SE-704 is a microprocessor based ground fault relay for resistance and solidly grounded systems. It offers very sensitive ground fault detection as low as 10 mA and can be used on systems with significant harmonic content. The SE-704 provides feeder level protection or individual load protection. The output contacts can be connected for use in protective tripping circuits or in alarm indication circuits. The analog output can be used with a PLC or a meter.
Littelfuse® Earth Leakage Monitor, Series: SE-704, 12/24 VDC, 0 to 5 VDC, 0 to 1 mA Analog Output, Isolated NO (1 Form A), NC (1 Form B) Output Contact, 24 to 12 AWG Wire Clamping Terminal, DIN Rail/Surface Mount, 3 in H x 2.2 in W x 4.5 in D

Specifications

 Analog Output 0 to 5 VDC, 0 to 1 mA
 Application Industrial Applications
 Brand Name Littelfuse®
 Dimensions 3 in H x 2.2 in W x 4.5 in D
 Manufacturer Part Number SE-704-0D
 Mounting Type DIN Rail/Surface
 Series SE-704
 Specifications Isolated NO (1 Form A), NC (1 Form B) Output Contact, 24 to 12 AWG Wire Clamping Terminal
 Standards/Approvals cCSAus File No. LR53428|UL File No. E340889|CE Certified|C-Tick Certified|FCC CFR47 Part 15 Subpart B
 Voltage Rating 24-Dec VDC

Features

▪ Universal power supply allows operation in application where one side of PT is faulted, provides flexibility for numerous applications
▪ Adjustable pickup (10 mA to 5 A) - adjustable trip setting provides a wide range of low level protection and system coordination
▪ Adjustable time delay (30 ms to 2 s) - adjustable trip delay allows quick protection and system coordination
▪ Form A and form B ground fault output contacts for operation of separate annunciation and trip circuits
▪ Analog output (0 to 5 VDC and 0 to 1 mA) allows for connecting an optional meter (PGA-0500) or control system
▪ CT-loop monitoring - alarms when CT is not connected
▪ Selectable fail safe or non-fail safe operating modes allows connection to shunt or undervoltage breaker coil
▪ Harmonic filtering eliminates nuisance tripping
▪ Non-volatile trip memory retains trip state when de-energized to simplify troubleshooting
▪ No calibration required, saves on maintenance cost
 
Time Zone 
 
 
 