▪ 8000 cycles mechanical durability |
▪ 8000 cycles electrical durability |
▪ Connector 1 cable 3/4 to 6 sq-mm, 3/4 to 4 sq-mm, 3/4 to 4 sq-mm, 3/4 to 2-1/2 sq-mm cable stiffness solid without cable end |
▪ 1.2 N-m on connector tightening torque |
▪ Shocks 22 gn for 20 ms conforming to IEC 60068-2-27, vibrations 5 Gn, 5 to 110 Hz conforming to IEC 60068-2-6 mechanical robustness |
▪ (2) 9 mm pitches |
▪ TC protective treatment |
▪ IP20 conforming to IEC 60529 deg of protection |
▪ -40 to 80 deg c ambient air temperature for storage |
▪ 960 deg c conforming to IEC 60695-2-1 fire-resistance |
▪ Icu = 50 kA at 230/240 VAC at 50/60 Hz, Icu = 1 kA at 48 VDC, Icu = 50 kA at 110 VAC 50/60 Hz, Icu = 1.5 kA at 24 VDC conforming to IEC 60947-2 |
▪ Category a conforming to IEC 60947-2, DC-12 conforming to IEC 60947-5-1, DC-13 conforming to IEC 60947-5-1 utilization category |
▪ 50/60 Hz conforming to IEC 60947-2 network frequency |
▪ 50% at 110 vac 50/60 Hz, 25% at 230/240 vac 50/60 Hz conforming to IEC 60947-2 |
▪ By clips mounting |
▪ Horizontal/vertical mounting position |
▪ Toggle control type |
▪ 277 vac 50/60 Hz conforming to CSA C22.2 no 14, 48 VDC, 250 vac 50/60 Hz conforming to IEC 60947-2, 277 vac 50/60 Hz conforming to UL 1077 rated operational voltage |
▪ 4 kV conforming to IEC 60947-2 rated impulse withstand voltage |
▪ 2 W power dissipation per pole |