| ▪ Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations |
| ▪ Tapered FNPT connection |
| ▪ 25% fill vertical and horizontal conduit sealing fittings for close turning radius |
| ▪ Chromate/epoxy powder coated/zinc electroplated finish |
| ▪ Smooth, rounded integral bushing in each hub to protect conductor insulation |
| ▪ Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity |
| ▪ Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub |
| ▪ Large opening for damming and filling |
| ▪ Restrict any explosion to the sealed off enclosure |
| ▪ Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures |
| ▪ Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps |
| ▪ Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location |
| ▪ Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure |