| ▪ When a 5000:5 ratio interposing CT is used, all displayed values are to be interpreted as kA rather than amps |
| ▪ Used with 30 ft of standard 4-wire telephone type cable connection |
| ▪ Use with D64RPB100 Series B1 digital ground fault relay |
| ▪ Continuous reading of actual ground fault current, employing auto ranging |
| ▪ Display of the pre-trip ground fault current, after a trip has occurred (flashing display) |
| ▪ Display of the trip current setting, after a test trip has been activated |
| ▪ Test and RESET pushbuttons |
| ▪ The RESET button must be held pressed before the test is pressed to invoke the test procedure |
| ▪ The function of this button can be enabled/disabled by inserting the interconnecting cable from the D64RPB100 relay into one of two sockets, TEST on or TEST off, on the right side of the display |
| ▪ Pushing verify pushbutton shows if D64RPB100 tripped due to a ground fault prior to loss of its control voltage red trip LED lights or if there was no ground fault green run LED light strip-green run LED lights |
| ▪ This indication will remain available for at least ten hours |
| ▪ The numerical LCD window displays actual ground fault current in amps |