Page Loading...
Schneider Electric
140ACO02000 SQD AN OUT 4CH CURR

Mouse over image to zoom, click to enlarge

Description: Schneider Electric Modicon™ Quantum™ Square D™ Analog Output Module, 4 Outputs, 12 to 30 V DC, 4 to 20 mA, 5.3 W Power, 0 to 60 deg C

Manufacturer PN: 140ACO02000

UPC:  59586112657

Kendall Electric Inc PN: 3959912

Invoice Description:

140ACO02000 SQD AN OUT 4CH CURR


SPEC SHEET

▸ See All in PLC Input-Output Analog Modules

 

Schneider Electric Modicon™ Quantum™ Square D™ 140ACO02000 Analog Output Module, 4 Outputs

Log In for Pricing and Availability

Note: Lead times are estimates only

 
 

Schneider Electric and Square D products are only sold to customers in our authorized sales territory. Please log into your account to see locally available product.

Description

Schneider Electric Modicon™ Quantum™ Square D™ Analog Output Module, 4 Outputs, 12 to 30 V DC, 4 to 20 mA, 5.3 W Power, 0 to 60 deg C

Specifications

 Amperage Rating 4 to 20 mA
 Application Modicon Quantum Automation Platform Applications
 Brand Name Square D
 Manufacturer Part Number 140ACO02000
 Number of Outputs 4
 PART NUMBER KEYWORDS 140ACO02000 ; 9114082 ; 785901792192 ; 78590179219 ; 03595861126572 ; 3595861126572
 Power Rating 5.3 W
 Standards/Approvals CE Certified|CSA C22.2 File No. 142|cUL Listed|FM Class 1 Division 2|PROP65: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.p65warnings.ca.gov|RoHS Compliant|UL 508
 Temperature Rating 0 to 60 deg C
 Voltage Rating 12 to 30 V DC

Features

▪ 900 us to +/-0.1% of the final value setting time
▪ Open circuit 4 to 20 mA fault type
▪ 480 mA bus current requirement
▪ <=5.3 W power dissipation
▪ 12 to 30 V external power requirement
▪ Standard module format
▪ 10 V/m 80 to 1000 MHz conforming to IEC 801-3-resistance to electromagnetic field
▪ -40 to 85 deg C ambient air temperature for storage
▪ 95% without condensation relative humidity
▪ <=5000 m operating altitude
▪ 4 LED green channel is turned on, 4 LED red channel fault, 1 LED green bus communication is present (active), 1 LED red external fault
▪ 4 output words addressing requirement
▪ 12 to 30 VDC loop voltage
▪ 7 to 30 V 20 mA voltage drop
▪ 4 to 20 mA 0 to 4096 counts, 12 bits bipolar current analog output range
▪ +/-0.2% of full scale at 25 deg C absolute accuracy error
▪ +/-1 LSB linearity
▪ +/-0.004% of full scale/deg C, +/-0.007% of full scale/deg C maximum accuracy drift according to temperature
▪ 500 VAC 47 to 63 Hz, 750 VDC for 1 min isolation between channel
▪ 3 ms update time
 
Time Zone 
 
 
 