| ▪ 900 us to +/-0.1% of the final value setting time |
| ▪ Open circuit 4 to 20 mA fault type |
| ▪ 480 mA bus current requirement |
| ▪ <=5.3 W power dissipation |
| ▪ 12 to 30 V external power requirement |
| ▪ Standard module format |
| ▪ 10 V/m 80 to 1000 MHz conforming to IEC 801-3-resistance to electromagnetic field |
| ▪ -40 to 85 deg C ambient air temperature for storage |
| ▪ 95% without condensation relative humidity |
| ▪ <=5000 m operating altitude |
| ▪ 4 LED green channel is turned on, 4 LED red channel fault, 1 LED green bus communication is present (active), 1 LED red external fault |
| ▪ 4 output words addressing requirement |
| ▪ 12 to 30 VDC loop voltage |
| ▪ 7 to 30 V 20 mA voltage drop |
| ▪ 4 to 20 mA 0 to 4096 counts, 12 bits bipolar current analog output range |
| ▪ +/-0.2% of full scale at 25 deg C absolute accuracy error |
| ▪ +/-1 LSB linearity |
| ▪ +/-0.004% of full scale/deg C, +/-0.007% of full scale/deg C maximum accuracy drift according to temperature |
| ▪ 500 VAC 47 to 63 Hz, 750 VDC for 1 min isolation between channel |
| ▪ 3 ms update time |